Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 12/10/2002 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 12/05/2002 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) HOLD DOWN NUTS NOT INSTALLED 2) SHEAR TRUSS AT GARAGE REQUIRED OSB TO ROOF SEE 501/S-4 3) NO CITY OF TUCSON APPROVED TRUSS DRAWINGS ON SITE 4) SHEAR WALL 4 MISSING WEDGE ANCHORS 5) EDGE NAILING OF WIRES NOT ALLOWED 6) NAIL PROTECT CONDENSATE LINES 7) NAIL PROTECT PEX WITHIN 1 1/2" OF STUD 8) DUCT RESTRICTED BY WIRES 9) ELECTRIC GFCI NOT WITHIN 24" OF KITCHEN SINK 10) HORIZONTAL VENT NOT ALLOWED SURFACE BELOW 42"-6" ABOVE FLOOR RIM |