Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T02CM04797
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2002 | BUILDING PRE-SLAB | Approved | IVRS - Inspection 0000* | |
| 11/20/2002 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) PLANS CALLS FOR A MONO POUR-SEE 11/15/02 WRITE UP YOU MUST HAVE PLANS REVISED AND APPROVED BY CITY OF TUCSON BEFORE PROCEEDING 2) VERTICAL REBAR MUST BE EMBEDED IN FOOTING | |
| 11/15/2002 | BUILDING PRE-SLAB | Denied | IVRS - Inspection 0999*/ 1) PLANS CALL FOR MONO POUR 2) CMU STEM REQUIRE VERTICAL #4 AT 48" ON CENTER WITH 2 #4'S CONT IN BOND BEAM AT TOP OF STEM 3) RELOCATE WATER LINE PRIOR TO FRAME INSPECTION GALV. PIPE NOT ALLOWED UNDER SLAB |