Inspection History: FRAMING

Permit Number - T02CM04793

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
02/24/2003 FRAMING Approved IVRS - Inspection 0000*/ 1) OK ON INTERMEDIATES
02/21/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NAIL ALL HOLDOWNS TO STUDS 2) ADD STUD AT KITCHEN RANGE VENT 3) BACKING AT TUB, TUB WALL 4) INSTALL BOTTOM PLATES AT SHEAR WALLS REQUIRED BOLTS 5) NEED LISTING ON OFF SET CLOSET RING 6) BLOCK DUCTS IN FURNACE ROOM 7) MOVE PEX AWAY FROM LIGHT CAN 12" 3 LIGHTS TOTAL 8) STRAP DRYER DUCT 9) TEST DRAIN WASTE AND VENT
02/04/2003 FRAMING Denied IVRS - Inspection 0950*/ 1) #950 WORK IS NOT COMPLETE ENOUGH TO INSPECT 2) PROVIDE ACCESS TO ROOF 3) PROVIDE TRUSS CALCS 4) NUMEROUS HOLDOWNS MISSING REPLACING WILL REQUIRE EPOXY SPECIAL INSPECTION