Permit: T02CM04786

Parcel: 13613001P

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/13/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) PLUMBING FINAL OK
2.) ALL CORRECTIONS MADE OK
3.) OK FOR C OF O PENDING ANY OTHER INSPECTION.
12/12/2002 PLUMBING - FINAL Denied 1.) RPZ'S REQUIRED TO BE ACCESSIBLE FOR SERVICE AND REPAIR
2.) INDIRECT WASTE PIPING BETWEEN 5-15 FEET TO BE TRAPPED.
3.) INDIRECT WASTE PIPING AT ICE MACHINE REQUIRES AIR GAP.
4.) HOT WATER PIPING AT HC LAVATORY TO BE INSULATED
5.) ABS AND PVC DRAIN PIPING AT 3 COMP SINK MAY NOT BE INTERMINGLED.
6.) REQUIRE 18" CLEARANCE IN FRONT OF 3" CO. AT 3 COMP SINK
7.) HAVE PLUMBER COMPLETE HIS PUNCH LIST BEFORE CALLING FINAL INSPECTION AS THIS LIST MAY NOT BE COMPLETE.
12/02/2002 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*PLEASE INSTALL ALL FIXTURES.
PROVIDE TESTING ON BACKFLOW DEVICES.