Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/22/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/20/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0160* |
| 08/19/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 08/12/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF UFER GROUND INSEPCTION OR INSTALL TWO 8' GROUND RODS CONNECTED TO PANEL WITH A CONTINOUS #4 GROUND 2) INSTALL A 20 AMP MAINTENANCE GFCI OUTLET FOR TEMP POWER 3) WE CANNOT INSPECT INTERMEDIATE ITEMS UNTIL STUCCO LATH IS APPROVED |
| 06/30/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |