Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM04784
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2003 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/25/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000* | |
08/22/2003 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) BLOCKING OF EXTERIOR SHEATHING 2) USE UL APPROVED TAPE AT DUCTS AND SEAL ALL TEARS AND OPENINGS | |
08/20/2003 | FRAMING | Denied | IVRS - Inspection 0160*/ 1) COMPLETE ITEMS FROM PREVIOUS INSPECTIONS 2) BRING J-BOXES TO SURFACE 3) SEAL VAPOR BARRIER 4) INSTALL PYRO-GARD AT GABLES 5) INSTALL WATER BOND 6) NAIL PLATE THROUGHOUT 7) LEAKS AT BOTH TUBS 8) INSTALL CO PER DETAIL 9) SEAL DUCTS 10) SUPPORT DUCTS PER CODE 11) TERMINATE DRYER VENT | |
08/19/2003 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) SEE INSPECTION FROM 8/12/03 2) PROVIDE PROOF OF EXTERIOR CLIPS/SHEATHING APPROVED INSPECTION 3) | |
06/30/2003 | FRAMING | Denied | IVRS - Inspection 0999* |