Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T02CM04784
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/17/2003 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000* | |
08/22/2003 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) HOLDOWNS AT REAR PORCH DELETED WITH APPROVED REVISION 2) SHEATHING ON EXTERIOR HAS BEEN RENAILED | |
06/30/2003 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) INSTALL AB'S WHERE NEEDED-MANY 2) PROVIDE PROPER COMBUSTIBLE CLEARANCE TO BE VENT 3) MISSING TRUSS H2.5'S NORTH OF MECHANICAL PLATFORM 4) REPLACE MECHICAL PLATFORM BLOCKING AT PLUMBING 5) CORRECT FRAME AT STOVE VENT DUCT 6) PROTECT CONDUIT AT KITCHEN SINK BOTTOM PLATE 7) FINISH FIREPLACE INSTALLS 8) CORRECT MIS-NAILED T.C. CLIPS 9) FINISH WIRING AT BEDFROOM/LIVING ROOM WALL (AROUND FIREPLACE) 10) MOVE MASTER SMOKEY OUT OF CLOSET 11) STRAP NON-CABIN TIED TOP PLATES 12) REPAIR FIREBLOCKING AT HOMERUNS AND ELSEWHERE IN SAME ROOM 13) SECURE 4 GANG AT ENTRY 14) BLOCK ENTRY DUCT BOOT 15) NEED DWV TEST NOTE: INTERMEDIATES/FRAME WILL NOT PASS UNTIL MESH IS DONE | |
06/02/2003 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection 0999*/ 1) REVISE DRAWINGS TO REFLECT AS BUILT 2) HOLDOWNS MISSING REAR PORCH |