Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/06/2003 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 09/30/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 01/03/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) GAS LINE NOT ALLOWED UNDER CONCRETE FLOOR THAT HAS ROOF OVER 2) GAS SLEEVES MUST BE PROPERLY SEALED/VENTED AND APPROVED ON PLAN 3) UNION AT ENTRANCE TO BUILDING MUST HAVE SHUT OFF VALVE 4) PROVIDE PROOF OF ELECTRIC SERVICE UPGRADE AS SERVICE CONDUCTORS APPEAR UNDER SIZED FOR 200 AMP PANEL 5) GAS LINE MUST BE ELECTRICALLY BONDED MASTER BEDROOM OK TO INSULATE AND DRYWALL MASTER BATH OK 6) REPLACE GAS UNIONS WITH LEFT AND RT HAND THREADED NIPPLE 7) "B" VENT SEALED WITH TAPE |