Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/06/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
09/30/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
01/03/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) GAS LINE NOT ALLOWED UNDER CONCRETE FLOOR THAT HAS ROOF OVER 2) GAS SLEEVES MUST BE PROPERLY SEALED/VENTED AND APPROVED ON PLAN 3) UNION AT ENTRANCE TO BUILDING MUST HAVE SHUT OFF VALVE 4) PROVIDE PROOF OF ELECTRIC SERVICE UPGRADE AS SERVICE CONDUCTORS APPEAR UNDER SIZED FOR 200 AMP PANEL 5) GAS LINE MUST BE ELECTRICALLY BONDED MASTER BEDROOM OK TO INSULATE AND DRYWALL MASTER BATH OK 6) REPLACE GAS UNIONS WITH LEFT AND RT HAND THREADED NIPPLE 7) "B" VENT SEALED WITH TAPE