Permit: T02CM04760

Parcel: 133110010

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM04760

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2004 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*/FIRE CAULK AROUND OPENING IN CEILING MECH EQUIPMENT ROOM
10/20/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/HOT WATER RETURN TO HEATER COILS IS OK. OK TO INSULATE
10/18/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/HOT WATER SUPPLY TO HEATER COILS IS OK. RETURN NOT HOLDING PRESSURE
09/09/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/I INSPECTED FIRE DAMPER OPENINGS IN STORAGE. OK FOR SHEET ROCK. OK TO COMPLETE DAMPERS
09/07/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) CHECKED FIRE DAMPER OPENINGS. PROVIDE SLEEVES AND ANGLE IRON. DAMPERS MUST BE ACCESSIBLE. PROVIDE FRAMING IN OPENINGS THRU SHEET ROCK. INSPECTED CHILLER, BOILER SUPPLY AND RETURN UP TO EXPANSION JOINTS