Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM04760

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/18/2004 ELECTRIC - INTERMEDIATE Approved
09/03/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) OK ABOVE ? EXCEPT AS NOTED 2) JUNCTION BOXES TO BE ACCESSIBLE
08/27/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK TWO WALLS AT STAGE RM 117
JUNCTION BOXES TO BE ACCESSIBLE
08/23/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/PARTIAL- OK SOUTH OF COLUMN Y-S ROOM 106 CEILING 1) NO MORE THAN 360DEGREE IN A CONDUIT RUN
08/20/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :OK WALLS ROOMS 111-113
07/26/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection BOXES WITH MORE THAN 200 VOLT TO GROUND TO HAVE SUSPENSION & COLOR CODE TO MATCH PHASE
CHECK CONDUCTOR FILL AT BOX W ROOM #105
OK WALL 100-104, 107-110
04/15/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK 3RD LIFT AT BLOCK.
03/25/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK 2ND LIFT BLOCK FOR BOXES
03/10/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ OK BOXES 1ST LIFT.