Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM04705
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/12/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NEED, TRUSS HIP GIRDER SHOP DRAWING, NEED TO KNOW IF 3 PT BEARING 2) NEED CANTILEVER DETAIL/EAST CORNER 3) FLAT VENT STILL NOT FIXED 4) USE LONG SWEEP AT FLOOR REPAIR 5) DAMPER MISSING SAME AS LAST INSPECTION. BACK PITCH ON FLAT VENT FROM LAST INSPECITON 6) NAIL SHEAR 2ND FLOOR CEILING INTER. | |
12/11/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) MISSED BACKING AT BAY WINDOW 2) FLAT VENT, PITCH ON HORIZONTAL PIPE BETWEEN 2 90 DEGREE, ALSO TUB SAN-TEE VENT TO BE AT 45 DEGREE OR VERTICAL 3) H.D.'S NOT BOLTED, #5 SHEAR WALL A.B. TOO BC 24" ON CENTER GARAGE 4) PEX WATER LINES TO CLOSE TO FURNACE VENT 5) STRAP AT DRYER VENT , NEED DRYWALL BACKING AT FURNACE 6) PEX AT WATER HEATER FLUE 7) UNCOVER LAUDNRY SINK DRAIN, USE LONG SWEEP 8) EXHAUST FAN MISSING DAMPER 1ST FLOOR BATH 9) SHEAR TRANSFER NOT NAILED 2ND FLOOR OSB ON TRUSSES 2-WALLS 10) STRAPS AT SHED ROOF TO WALL MISSING NAILS AT LEDGER 13) NO WATER IN DWV |