Permit: T02CM04679

Parcel: 125090780


Addresses:

2803 E VIA ROTUNDA

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
06/02/2004 ROOF NAILING Approved IVRS - Inspection :*
03/31/2004 ROOF NAILING Denied IVRS - Inspection 0999*/ 1) DETAIL 10/S4 REQUIRES 1" X 8" BOLTS-1/2" USED 2) ROOF JOIST CONNECTION STEEL STRUCTURE IS NOT BUILT PER 19/S3. HAVE ENGINEER OF RECORD/SPECIAL INSPECTOR CERTIFY STEEL CONSTRUCTION 3) HANGERS NOT PER 9/S4 4) OSB PANELS MUST SPAN 2 BAYS- ( 3 JOIST) 5) OSB PANELS CANNOT BE INSTALLED WITH GRAIN PARALLEL TO SUPPORTS