Permit: T02CM04668

Parcel: 10703141C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
01/08/2003 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*
FCU WALL MOUNTED FAN COIL
1.) REFRIG. LINES IN CONTACT (COPPER TOUCHING)
WITH SPRINKLER LINE ABOVE CEILING GRID.
2.) WHERE IS CONDENSATE TERMINATION FOR AIR HANDLER, WALL? MOUNTED?
FOR FINAL, HAVE ROOF ACCESS AVAILABLE. WILL CHECK COND. DRAINS. PROPER FUSING ETC.
12/17/2002 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*APPROVED PLANS DO NOT INCLUDE SHT. M1
HAVE MECH. PLAN AVAILABLE FOR NEXT INSP.
NOTE SUPPLY RETURN DUCTS ABOVE GRID & CEIL. TILES NEED TO BE PROPERLY INSULATED. DOORS AT REAR OF SPACE ARE GOING TO ALLOW INFILTRATION OF HOT, HUMID AIR IN SUMMER. CONDENSATION COULD BE A POSSIBLE PROBLEM.