Permit: T02CM04668

Parcel: 10703141C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/29/2003 ELECTRIC - FINAL Approved
01/16/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SENT TO TEP ON 1/17/03 AT 9:15AM OK TO CLEAR.
01/13/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*PLEASE CORRECT THE FOLLOWING.
1.) EXPLAIN CHANGE IN SERVICE DISCONNECTS.
2.) CHANGE NUMBERING TO MATCH PLAN.
3.) RE-INSTALL UFER GROUND TO SWITCHES DISCONNECTS.
4.) RE-FUSE PER PLAN. ADD REJECTION CLIPS WHERE REQUIRED.
5.) LEAVE GUTTER OPEN FOR REINSPECTION.
6.) REVISE PLAN TO REFLECT CHANGES.
THANKS RECALL WHEN SERVICE IS COMPLETE.
01/07/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*PLEASE HAVE PLANS ON SITE THIS IS LATEST I CAN BE HEAR.