Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2003 | ELECTRIC - FINAL | Approved | ||
| 01/16/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 1/17/03 AT 9:15AM OK TO CLEAR. | |
| 01/13/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0210*PLEASE CORRECT THE FOLLOWING. 1.) EXPLAIN CHANGE IN SERVICE DISCONNECTS. 2.) CHANGE NUMBERING TO MATCH PLAN. 3.) RE-INSTALL UFER GROUND TO SWITCHES DISCONNECTS. 4.) RE-FUSE PER PLAN. ADD REJECTION CLIPS WHERE REQUIRED. 5.) LEAVE GUTTER OPEN FOR REINSPECTION. 6.) REVISE PLAN TO REFLECT CHANGES. THANKS RECALL WHEN SERVICE IS COMPLETE. |
|
| 01/07/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*PLEASE HAVE PLANS ON SITE THIS IS LATEST I CAN BE HEAR. |