Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T02CM04657
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2002 | FRAMING | Approved | IVRS - Inspection 0000* | |
12/04/2002 | FRAMING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) SEE LAST INSPECTION | |
12/02/2002 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) PLANS CALL FOR STUDS TO BE HEMP FIR STD OR STUD GRADE 2) NO MENTION OF USING FINGER JOINTED SPRUCE PINE FIR STUDS. 3) PRVOIDE A35'S FROM TRUSS BOTTOM CHORD TO DOUBLE TOP PLATE PER 3/SD-2 ALL SHEARWALLS 3) GABLE END DIAGONAL VRACING NOT PER PLAN 2/SD-2 4) MAKE ALL JOINTS PRECISE |