Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 09/23/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/20/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ELECTRIC EXTERIOR METAL BOXES MUST HAVE WIRING INSTALLED AND GROUNDED 2) OUTLET ON EAST WALL OF FAMILY ROOM MUST BE MOVED NORTH TO WITHIN 6' OF HALL DOORWAY 3) INSTALL PROTECTION PLATES ON ELECTRIC AND PLUMBING WHERE NEEDED 4) NEED YELLOW PERMIT CARD ON SITE 5) FHA STRAP DRYER DUCT AT TOP PLATES 6) NOTE: DISTRIBUTION SYSTEM IS LARGER THAN PLAN CALLS FOR |
|
| 08/27/2004 | FRAMING | Partial Approval | IVRS - Inspection :MASONRY FIREPLCE/PARTIAL HEARTH OK DAMPER TO HAVE A LOCK TO KEEP DAMPER OPEN BECAUSE OF GAS PIPING, TO HEARTH NEXT INSP FINAL LIFT FROM BOND BEAM |
|
| 06/09/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |