Permit: T02CM04644

Parcel: 120061230


Addresses:

424 E PRESIDENT ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/26/2003 FRAMING Approved IVRS - Inspection 0000*
09/25/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) BLOCK 3 SIDES MECHANICAL VENTS 2) 1" CLEARANCE FLUE PIPES TO COMBUSTIBLES 3) LEAK AT WASHER 4) FIRE BLOCK ALL FURR DOWN AREAS 5) INSTALL COMB/RELIEF VENTS TOP AND BOTTOM UTILITY ROOM 6) PLAN CALLS FOR GAS FURNACE AND RANGE 7) INSTALL LONG SWEEPS KITCHEN VENT 90 DEGREE ELBOWS 8) STRAP ALL PLUMBING AND ELECTRIC HOLES WHERE NAILS MIGHT PENETRATE 9) GAS NOT INSTALLED PER PLAN 10) STOPPED INSPECTION 11) SUBMIT ASBUILT REVISIONS TO PLAN CHECK FOR APPROVAL
09/04/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*
08/26/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) STRAP ACCROSS BEAM SPLICES 2) FILL IN SOLIDLY UNDER BEAM BEARING 3) BEAM MISSING FRONT PORCH 4) INSTALL POSITIVE CONNECTION ALL BEAMS INTO MASONRY 5) NEED LADDER ACCESS TO INSPECT ROOF SHEATHING