Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK FOR C OF O. |
| 09/19/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE REQUIRES 3' OF CLEARANCE IN FRONT OF ALL THE WAY DOWN TO THE GROUND - GAS METER, STUB OUT, TELEPHONE. 2) SERVICE REQUIRES PERMANANT ADDRESSING. 3) GFI KITCHEN SINK DOES NOT SHUT OFF OTHER RECEPTACLES NEXT TO IT. 4) REAR OUTSIDE GFI NOT WORKING, CHECK FRONT ONE. 5) SMOKE DETECTORS NOT WORKING. 6) WHERE IS METER BOND? 7) MECHANICAL BOX ON ROOF BLOCKING PANEL REMOVAL. |
| 09/15/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
1) PROVIDE VACCUM BREAKER AT HOSE BIBS 2) COMPLETE TWO WAY CO 3) CO MISSING AT LAUNDRY WASHER SEE PLAN 4) PLEASE PRVOIDE SIGN "THIS BLDG HAS NON METALLIC WATER PIPING" FASTENED INSIDE ELECTRIC SERVICE |