Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/12/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 11/10/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) ROOF HAS BEEN HOT TARRED-NEGATING ROOF NAIL INSPECTION 2) INSULATION MUST BE REMOVED FOR INTERMEDIATE INSPECTIONS |
| 11/06/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) ADDN NOT BUILT PER PLAN-RAFTERS AT 20" ON CENTER. SHOULD BE 16" ON CENTER 2) PORCH SOULD BE 23' LONG ACTUAL 27' 3) 4 X 8 BEAM SPANS 14' SHOULD BE 11' 4) RAFTERS NOT CLIPPED AT CMU WALL SEE 1/4 5) WATER HEATER "B" VENT REQUIRES 1" TO COMBUSTIBLES 6) BUILD TO PLAN OR HAVE PLAN REUSED TO ASBUILT AND APPROVED BY CITY OF TUCSON |