Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/23/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR C OF O |
| 07/21/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) USE A ROMEX CONNECTOR AT DISCONNECT 2) CONNECT PLASTIC HOSE TO COPPER WITH A FITTING CONNECT OVERFLOW SENSOR. USE HOSE CLAMPS ON PLASTIC HOSE CONNECTIONS |
| 07/08/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999* 1) SERVICE DISCONNECT FOR AIR HANDLER ON 1ST FLOOR NOT ACCESSABLE. 2) PERMANENTLY LABEL EQUIPMENT. 3) CONDENSATE CANNOT TERMINATE ONTO A HARD SURFACE. 4) LABEL FAN COIL W/ PROPER HEAT KIT INSTALLED AND FUSE ACCORDINGLY. 5) FINISH CONNECTING DIFFUSERS. 6) 3RD FLOOR AIR HANDLER PROVIDE A TRAP ON CONDENSATE DRAIN LINE. DO NOT USE T-BAR WIRE FOR SUPPORT. FINISH CONNECTING DIFFUSERS. 7) NEED TO SEE ACCESS PANEL 4TH FLOOR RESTROOM. LABEL PANELS. |
| 07/03/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*NOBODY ON SITE; CALL FOR REINSPECTION |
| 06/19/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) NEED TO SEE FAN COIL 1ST FLOOR CORRIDOR & CONDENSER 2) FINISH INSTALLING ACCESS PANELS TO FIRE DAMPERS A/C UNIT ON ROOF IS OK. OK FOR TEMP C OF O |