Permit: T02CM04617


Addresses:

250 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T02CM04617

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) OK FOR C OF O
07/21/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) USE A ROMEX CONNECTOR AT DISCONNECT 2) CONNECT PLASTIC HOSE TO COPPER WITH A FITTING CONNECT OVERFLOW SENSOR. USE HOSE CLAMPS ON PLASTIC HOSE CONNECTIONS
07/08/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999* 1) SERVICE DISCONNECT FOR AIR HANDLER ON 1ST FLOOR NOT ACCESSABLE. 2) PERMANENTLY LABEL EQUIPMENT. 3) CONDENSATE CANNOT TERMINATE ONTO A HARD SURFACE. 4) LABEL FAN COIL W/ PROPER HEAT KIT INSTALLED AND FUSE ACCORDINGLY. 5) FINISH CONNECTING DIFFUSERS. 6) 3RD FLOOR AIR HANDLER PROVIDE A TRAP ON CONDENSATE DRAIN LINE. DO NOT USE T-BAR WIRE FOR SUPPORT. FINISH CONNECTING DIFFUSERS. 7) NEED TO SEE ACCESS PANEL 4TH FLOOR RESTROOM. LABEL PANELS.
07/03/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*NOBODY ON SITE; CALL FOR REINSPECTION
06/19/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000* 1) NEED TO SEE FAN COIL 1ST FLOOR CORRIDOR & CONDENSER 2) FINISH INSTALLING ACCESS PANELS TO FIRE DAMPERS A/C UNIT ON ROOF IS OK. OK FOR TEMP C OF O