Permit: T02CM04617


Addresses:

250 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T02CM04617

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2003 MECHANICAL - ABOVE CEILING Approved
06/11/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) THREADED ROD FROM PIPING SUPPORT BLOCKING ACCESS TO BLOWER COMPARTMENT ON AIR HANDLER. WATER PIPE BLOCKING ACCESS TO FILTER. 2) PROVIDE RETURN AIR IN MAIN LOBBY 1ST FLOOR FROM AH-1. ALSO PROVIDE OUTSIDE AIR INTAKE. 3) NEED TO SEE CONDENSATE OK FOR SHEET ROCK
06/03/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) INSPECTED ROUGH DUCT, FLEX AND DIFFUSERS IN CORRIDOR AND TRAINING ROOM ON 2ND FLOOR-NOTE: WHAT ABOUT ACCESS TO FIRE DAMPERS ABOVE BATHROOMS ?
05/16/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) INSPECTED FIRE DAMPERS IN RESTROOM SHAFTS OK TO COVER
05/09/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) Open walls in bathroom shafts to confirm angle iron on back side of dampers.
2.) Provide access panels to all motors on fire dampers & access in ducting.
04/30/2003 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*INSPECTION ON 3RD FLOOR. OK FOR CEILING TILES.