Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T02CM04617
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2003 | MECHANICAL - INTERMEDIATE | Approved | ||
04/25/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* INSPECTED FIRE DAMPERS IN SHAFT WALLS OK TO SHEET ROCK & INSTALL ANGLE IRON FRAMES. STILL NEED TO SEE EXHAUST DAMPERS. |
|
04/10/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*INSPECTED FIRE DAMPER OPENINGS. OK TO PROCEED. NEED TO SEE JOINTS FIRE CAULKED, COMPLETE FRAMING AROUND DAMPERS, & ANGLE IRON INSIDE SHAFTS. OPENINGS MUST HAVE MIN 1/4" CLEARANCE AROUND DAMPERS. | |
04/01/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* INSPECTED GREASE DUCTS ON 4TH FLOOR OK TO COVER. |
|
03/31/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*INSPECTED GREASE DUCTS ON 4TH FLOOR. PROVIDE MIN 6" CLEARANCE INSIDE SHAFT. RECALL FOR INSPECTION. | |
03/26/2003 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*INSPECTED GREASE DUCTS ON 2ND & 3RD FLOOR. OK TO PROCEED W/SHAFT. PARTIAL INSPECTION ON ROUGH DUCT. O.K. TO PROCEED. GREASE DUCT SYSTEM NOT SHOWN ON PLANS PLEASE PROVIDE DETAILS. |