Permit: T02CM04617


Addresses:

250 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T02CM04617

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2003 MECHANICAL - INTERMEDIATE Approved
04/25/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
INSPECTED FIRE DAMPERS IN SHAFT WALLS OK TO SHEET ROCK & INSTALL ANGLE IRON FRAMES. STILL NEED TO SEE EXHAUST DAMPERS.
04/10/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTED FIRE DAMPER OPENINGS. OK TO PROCEED. NEED TO SEE JOINTS FIRE CAULKED, COMPLETE FRAMING AROUND DAMPERS, & ANGLE IRON INSIDE SHAFTS. OPENINGS MUST HAVE MIN 1/4" CLEARANCE AROUND DAMPERS.
04/01/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
INSPECTED GREASE DUCTS ON 4TH FLOOR OK TO COVER.
03/31/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTED GREASE DUCTS ON 4TH FLOOR. PROVIDE MIN 6" CLEARANCE INSIDE SHAFT. RECALL FOR INSPECTION.
03/26/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*INSPECTED GREASE DUCTS ON 2ND & 3RD FLOOR. OK TO PROCEED W/SHAFT.
PARTIAL INSPECTION ON ROUGH DUCT. O.K. TO PROCEED.
GREASE DUCT SYSTEM NOT SHOWN ON PLANS PLEASE PROVIDE DETAILS.