Permit: T02CM04617


Addresses:

250 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM04617

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/06/2003 ELECTRIC - ABOVE CEILING Approved
06/11/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) WILL NEED PROPER ACCESS TO ABOVE CEILING 2) JUNCTION BOXER 22 1/2" X 30" MINIMUM 3) THIS ACCESS TO EASILY RE ? ALL BOXER NOTE: SEE ATTACHMENT CONCERNING SERVICE EQUIPMENT
06/05/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) APPROVED AT K.B. TENNANT SPACE AND 2ND FLOOR CORRIDOR 2) 4TH FLOOR CORRIDOR APPROVED
05/14/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
05/06/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NOTE: AIR HANDLERS IN VIOLATION OF 110-26, INSUFFIENCT CLEARANCE S.
04/30/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) BEAM CLAMP NOT LISTED FOR GROUNDING USE AN APPROVED CLAMP.
2.) FINISH BOLTING TRANFORMER TO DECK
3.) FINISH ATTACHMENT OF VDV SUPPORT WIRE.
4.) OK ABOVE CEILING 3RD FLOOR EXCEPT AS NOTE OK PNL 3LA & 3LB AND XFMR T-3.
04/11/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*