Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T02CM04617
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2003 | ELECTRIC - INTERMEDIATE | Approved | ||
06/09/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO ENERGIZE 250 S. CRAYCROFT ORIGINAL TEMP POWER FOR HOUSE PANEL | |
05/28/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) UNDER GROUND FOR CANOPY LIGHTING-APPROVED | |
05/23/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TEMP POWER FUEL AND TEST FOR SHELL 2) BOND FOR TEMP POSTED ALL INSPECTORS HAVE SIGNED OFF APPROVING TEMP POWER RMAJUTA | |
05/20/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* FILL IN SIGN OFF SHEET. GFI 1200 AMP REQUIRE PERFORMANCE TEST PER CODE 230-95 1) WILL NEED LETTER OF SERVICE AND SUB PANEL TORQUEING 2) WILL NEED ACCURATE REVISED PLANS SHOWING MATCHING SUITE NUMBERS 30 NEED SIZE OF SECONDARY CONDUCTORS. NEED LETTER FROM ENGINEER 4) WILL NEED PROPERLY SIZED CONCRETE APRON | |
04/21/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*3RD & 4TH FL. CONF. ROOM SOFFITS, 2ND, 3RD &4TH FL ELEV. SOFFITS. 2ND, 3RD AND 4TH BATH WALK. |
|
04/11/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ELEVATOR @ PIT. INTERMEDIATE APPROVED FOR 2 LIGHTS AND GFI APPROVED. 2ND FLOOR K.B. BATHWALKS AND HALLWAY. SHELL 2ND FLOOR SOFFITS RECESSED CANS AND VOLENCE LIGHTING APPROVED. 2ND FLOOR K.B BATHWALK |
|
04/01/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*ALL WALK 3RD AND 4TH FLOOR, LESS BATHROOM. INTERMEDIATE APPROVED. | |
03/27/2003 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK 3RD FLOOR AS MARKED ON PLANS OK 4TH FLOOR AS MARKED ON PLANS. 1.) CK FITTINGS & CONDUIT STRAPING AS PER CODE 348 2.) NO MOR THAN 360 IN A RUN. |
|
03/25/2003 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*WOULD LIKE INSPECTION W/OUT PERMITS. PERMIT BEING HELD BECAUSE OF WASTE WATER PROBLEM ON PLAN. MY ANSWER, CALL SUPERVISOR. |