Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) APPROVED REPLACEMENT CORDS IN USE |
| 06/26/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) THESE CORDS ARE NOT ACCEPTABLE AS PER 400-7 AND 400-8 OF THE NEC |
| 06/25/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* ELECTRIC INSTALLATIONIS OK. PLEASE VERIFY CORDS AS PER LAST INSPECTION. |
| 06/20/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) CORDS USED FOR GARAGE DOOR MOTOR'S LOOK TO BE EXTENDED CORD 16-3. PLEASE VERIFY MANUFACTURERS LISTING FOR CORDS 2) FINISH #1 OF PREVIOUS INSPECTION-METAL NOT APPROVED |