Permit: T02CM04592

Parcel: 135084630


Addresses:

1345 S KOLB RD #648


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T02CM04592

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/07/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
11/01/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*CANNOT GUARANTEE A 7:30 - 8:00 INSPECTION RESCHEDULE & LEAVE OPEN OR LEAVE A PHONE # TO CALL PRIOR TO INSPECTION.
10/18/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*CORRECTIONS REQUIRED MARK THE MAIN DISTRIBUTION PANEL DIRECTORY WITH APTMT. NUMBERS. #748 1.) CLEAN THE ELECTRICAL OF ALL DIRT AND REMOVE PAINT FROM THE BUSS BARS. USE WIRE BRUSH. 2.) REMOVE THE FEED WIRES FROM THE TERMINAL LUGS AND WIRE BRUSH THE ENDS CLEAN. APPLY A NEW COAT OF NOALOX ON ENDS AND RETERMINATE. 3.) THE 99 NEC REQUIRES ALL LIGHT SWITCHES BE GROUNDED. LEAVE A GROUND WIRE PIGTAIL AT EACH SWITCH BOX FOR THIS PURPOSE. 4.) HARD WIRE SMOKE DETECTOR OUTLET IN BEDROOM AND HALLWAY. 5.) COVER UNSUED CONDUIT KNOCKOUT AT TOP OF PANEL. 6.) COMPLETE THE WIRING OF THE A/C FAN UNIT. 7.) REPLACE SET SCREW IN 1"EMT CONNECTOR AT TOP OF PANEL.