Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T02CM04588
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2003 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection 0000* | |
10/02/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* | |
08/18/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* | |
08/04/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* OK @ S W CORNER WALL A-G | |
07/30/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* 1) BG RES WALL OK. 2) PER CONSERVATION REBAR FROM EXTERIOR TO INTERIOR FOOTING. (REF M3/23) | |
07/25/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* A4 OK TO CLOSE & POUR | |
07/24/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) D6, A3 AND C6 | |
07/23/2003 | STEM WALL/RETAINING WALL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) 2:40 PM SITE LOCKED | |
07/21/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) ? STEEL-OK A3 AND A4 2) D6 OK TO POUR | |
07/18/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) STAIRS IN VALVE VAULT OK | |
07/17/2003 | STEM WALL/RETAINING WALL | Not ready for Inspection | IVRS - Inspection 0000*/ VALVE VAULT STAIR NOT READY. PLEASE COMPLETE TREAD FORMS, NOSE BARS AND POST INSERTS. 2) REINFORCEMENT FOR MATS DOES NOT CONFORM TO PLAN. IS THERE AN RFI OR DESIGN CHANGE? | |
07/16/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) A-2 CLOSED AND READY TO POUR 2) E-6 OK TO CLOSE AND POUR 3) ITEMS 2 (ABS FROM 7-2) WERE TAKEN CARE OF AND PLACEMENT OF CONCRETE OK PER BOB LENON OF TUCSON WATER 4) ITEM D FROM 7/2/03 HAS BEEN ADDRESSED IN RFI #39 DEGREE | |
07/09/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/1) OK TO CLOSE AND POUR A-1. 2) STEEL OK IN A-5, A-6, B-6. 3) PLEASE PROVIDE WRITTEN RE-INSPECTION REPORT FROM SPEC. INSP. CONCERNING ITEMS A,B,& C NOTED ON 7/2/03. 4) PLEASE PROVIDE ENGINEERING EVALUATION CONCERNING ITEM D FROM NOTES ON 7/2/03. | |
07/02/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* 1. INSP OF DAMAGED VALVE VAULT AREA: A) #5 HOOKS AT TOP OF WALL HAVE NOT BEEN COMPLETED. B) OUTSIDE FACE OF REPAIR DOES NOT APPEAR TO COME TO TOP OF WALL. C) THERE ARE MISSING HORIZONTAL REINFORCEMENT BARS AT BOTTEM OF OUTSIDE FACE. D) YOU WILL NEED TO HAVE 2" CLEAR FROM VERTICALS TO FORM. I NOTICED THAT PART OF THE AREA YOU CHIPPED OUT ONLY HAS 1/2" OF COVER ON VERTICAL STEEL. | |
06/26/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) STEEL IN A2 AND E6 OK 2) READY TO CLOSE AND POUR SOUTH F6 | |
06/23/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) STEEL IN F6 OK 2) F5 READY TO CLOSE AND POUR | |
06/18/2003 | STEM WALL/RETAINING WALL | Partial Approval | 1) STEEL IN A1-OK | |
06/12/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) F-3 BLOCKED OUT AROUND VENTS 2) STEEL IN C6 AND D6 OK | |
06/09/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) I NEED SPECIAL INSPECTION REPORT FROM 6/6/03 2) STEEL OK IN D1, C1 AND F4 3) EXTRA REINFORCEMENT NEEDED FOR VENTS IN F-3 | |
06/05/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*/ 1) WALL AT TOP OF F2-OK 2) WALL AT TOP OF EL REQUIRES ADDITIONAL VERTICAL REINFORCEMENT PER DETAIL A/24. SPECIAL INSPECTOR IS ON SITE AIDING IN ADDITIONAL PLACEMENT. CONFIRMS ADDITIONAL VERTS. | |
05/30/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* STAIRS IN RESERVOIR OK |