Permit: T02CM04576

Parcel: 120082440


Addresses:

4718 S 6TH AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/12/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
04/07/2006 PLUMBING - INTERMEDIATE Partial Approval 5.9 PSI 9:38
PRESSURE TEST OK
OK TO COVER
SECURE CLOSET FLANGES TO FLOOR W/CORROSION RESISTANT ANCHORS
03/21/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
5 PSI AT 9:58 ZERO 10:08
CORRECT LEAK
PRESSURE TEST BEFORE INSPECTION.
03/08/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSTALL HOT WATER LINE PER PLAN AND TEST
3" CLEANOUT PLUG GLUED IN
GAUGE STUCK ON 4 PSI -- NOT OPERATING
REPLACE CLEAN OUTS, INSTALL ABOVE TOILET.
PROVIDE 5 PSI TEST
03/02/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 3" SANT INSTALLED UPSIDE
2. COMBO NOT CORRECT FITTING FOR FIXTURE CONNECTION A SAN TEE IS REQUIRED TO PROPERLY VENT FIXTURE (2X1 1/2) SANITARY TEE.
3. SWEEP REQUIRED FOR HORIZONTAL TO HORIZONTAL CHANGE OF DIRECTION.
4. 1 1/2" TRAP ARM IS MAX SIZE FOR LAVATORY
RETEST AND RECALL FOR INSPECTION.
02/09/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE A 3" VTR
REPLACE DAMGED SANTEE ON VENT
PROVIDE PROPER DRAINAGE FITTINGS FOR LAVATORY'S
REMOVE CONCRETE FROM COPPER WATER SUPPLY
PROVIDE A 5 PSI AIR TEST ON UNDERGROUND AND INTERMEDIATE PIPING (DWV)
01/17/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FLOOR AND WALLS HAVE BEEN COVERED
PROVIDE HISTORY OF PLUMBING INSPECTIONS OR UNCOVER ALL PLUMBING AND PROVIDE A WATER TEST SYSTEM