Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 08/11/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/1)RECEPT. IN STOREROOM NEEDS TO BE RE-INSTALLED IN BOX. INSTALL COVER PLATE. 2)OUTSIDE RECEPT. WEST OUTSIDE WALL NEEDS TO BE GFI? 3)RECEPT. IN WOMENS RESTROOM NOT INSTALLED 4)RE-SUPPORT BOX OUTSIDE BY WOMENS RESTROOM 5)ELECTRICAL INSTALL FOR OFFICE INSIDE & OUT NOT INSPECTED. UNCOVER DRYWALL ABOVE EACH RECEPT. 12"X12" AND BY EACH LIGHT FIXTURE TO INSPECT WIRING METHODS. 6)PLANS CALL FOR 200 AMP SERVICE-100AMP IS INSTALLED, REVISE PLANS OR INSTALL 200AMP 7)NEED TO VERIFY WATER/GAS PIPE BONDING 8)UNCOVER UNDERGROUND PIPING FOR INSP. 3 AREAS 1-IN MIDDLE - 1 EACH END. 9)QUARTZ SECURITY LIGHTING NOT APPROVED AS INSTALLED. VIOLATION COT LIGHTING ORDIN. |