Inspection Status: Not ready for Inspection
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2002 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* 1) ELECTICAL SERVICE WIRES FROM POWER POLE TO PT. OF ATTACHMENT ARE UNDERSTRAIN FROM NEIGHBORING TREES. 2) OUTLET IN BEDROOM ADDITON TO REMAIN AN UNGROUNDED TYPE, OR INSTALL AGFCI. 3) CHANGE FUSES N A/C TO 50AMP. 4) ONLY TWO WIRES IN FEEDER TO HVAC. USING CONDUIT AS A BOND TO GROUND, IT ISN'T CONNECTED N PLACES 5) GAS PIPE NOT TO BE IN GROUND ON WEST SIDE. 6) EAST SIDE REQUIRES 1HR PROTECTION, WAS WEST SIDE EXEMPT BY PLAN CHECK. 7) ELECTRICAL SERVICES HAS MORE THAN SIX SWITCHES REQS A BACKFLED BREAKER AT MAIN, WITH HOLD DOWN KIT. |
| 10/11/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PAPERWORK FROM PREVIOUS INSPECTION MUST BE PRESENT FOR THIS INSPECTION TO OCCUR |
| 10/10/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0945* |