Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*PLBG. FINAL IS OK OK FOR C OF O. |
|
| 01/29/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) FLOW CONTROL MUST BE LOCATED UP STREAM OF P-TRAP WHEN VENTED 6" ABOVE FLOOD RIM LEVEL OR IF LOCATED DOWN STREAM THEN VENT MUST GO TO ATMOSPHERE | |
| 01/27/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) HAND SINK TRAP ARM TO BE NO LESS THAN 1 PIPE SIZE SMALLER THAN TRAP. 2.) PLACE ELBOW ON CONDENSATE DRAIN TO FLOOR SINK 3.) SCREEN MISSING FROM FLOOR SINK. 4.) CLEAN OUT FOR MOP SINK REQUIRES 18" CLEAR SPACE. ESCUCHEON PLATE IS BLOCK BY MOP SINK. 5.) I DID NOT CHECK GREASE TRAP FITTINGS AS THEY ARE OUTSIDE UNDERGROUND. |