Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04538
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 01/15/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* 1.) PROVIDE CLEARANCE FOR ELEVATOR DISCONNECT & ID DESK. 2.) TIE UP FLEX ABOVE DISCONNECT, SUPPORT ONE HOLE STRAP BY VENTS. 3.) ID SHUNT TRIP PNL & CB. 4.) PROPERLY LABEL PNL E. 6.) NEED IN INSPECT PIT & ROOF LADDER. 7.) FINISH FIRE ALARM CONTROL WORK IN PLAN. |