Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02CM04528
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/10/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
02/19/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* CONTR. TO UPDATE PANEL SCHEDULES TO REFLECT NEW AREA INSTALL |