Permit: T02CM04519

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
10/23/2003 ELECTRIC - UNDERGROUND Approved
07/24/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ OK LAST 10' TO BLDG. 2-4" PVC. 1) SUPPORT 1" PVC FOR CONTROL WIRE IN TRENCH.
07/18/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ OK 2-4" PVC PULLBOX TO TEP XFMR SHORT 10', PULLBOX TO BLDG SHORT 10'.
07/03/2003 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection 0000*COSTUMER HAD QUESTIONS ABOUT TRENCH
05/18/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* 1) A CONDUIT RUN CAN HAVE NO MORE THAN 360 IN A RUN
05/14/2003 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*OK 2-3" PVC UNDERSLAB.