Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2002 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection 0000* | |
| 12/17/2002 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection 0999* 1.)SERVICE ENTRY CABLES FROM TRANSFORMER WILL HAVE TO BE 3' AWAY FROM WINDOW ONCE IN 2.) SERVICE NEEDS MAIN FUSES IN AND ADDRESS 3.) NEUTRALS FROM MAIN GUTTER TO BE BROUGHT DOWN AND BONDED AT MAIN DISCONNECTS FOR PANELS A-1 A-2 AND INSTALL FUSES 4.) MOVE CONDUCTORS DIGGING INTO LUG IN GUTTER. 5.)ID PANELS A1-A2. THIS IS FOR POWER RELEASE ON A1 & A2 OTHERS TO BE INSPECTED FIRST. |