Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 12/24/2002 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*OK TCO FOR MOVING IN FURNITURE. 1.) RISE FROM SIDE WALK TO FRONT ENTRANCE IS 7". FRONT RAMP WILL NEED TO COMPLY WITH ADAAG%8.33 (1:12) SLOPE. |
|
| 12/23/2002 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) PER REHABILITATION CODE: 1 EXIST ACCEPTABLE ON 1ST FLOOR IF TRAVEL DISTANCE LESS THAN 7S'. 2 EXIST REQUIRED/2 EXIST FOR ABLE BODIED. 2.) PER ADAAG 4.1.6(2) AT SOUTH EXIST IS TECHNICALLY IFEASIBLE TO REDUCE RAMP SLOPE FROM 23% TO 8.3% PER ADAAG 4.1.6.(H) APPROPRIATE ACCESSIBLE SIGNAGE INDICATING LOCATION OF ACCESSIBLE ENTRANCE WILL BE REQUIRED AT SOUTH DOOR. 3.) AT FRONT EAST DOOR PROVIDE APPROACH RAMP OF 1:12 MAX WITH WINGS OF 1:10 MAX. |
|
| 12/19/2002 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) THRESHOLD INTO HANDICAPPED RESTROOMS MUST COMPLY WITH APAAG GUIDE LINES. 2.) MENS'S HC RESTROOM WILL NEED 18" CLEAR FROM WALLS OR OBSTRUCTIONS TO CENTER OF TOILET 3.) I WILL REVIEW SOUTH RAMP REGS AND LET YOU KNOW. |