Permit: T02CM04516

Parcel: 117130400


Addresses:

130 S SCOTT AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
06/19/2008 BUILDING - FINAL Approved IVRS - Inspection :*
12/24/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*OK TCO FOR MOVING IN FURNITURE.
1.) RISE FROM SIDE WALK TO FRONT ENTRANCE IS 7". FRONT RAMP WILL NEED TO COMPLY WITH ADAAG%8.33 (1:12) SLOPE.
12/23/2002 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) PER REHABILITATION CODE: 1 EXIST ACCEPTABLE ON 1ST FLOOR IF TRAVEL DISTANCE LESS THAN 7S'. 2 EXIST REQUIRED/2 EXIST FOR ABLE BODIED.
2.) PER ADAAG 4.1.6(2) AT SOUTH EXIST IS TECHNICALLY IFEASIBLE TO REDUCE RAMP SLOPE FROM 23% TO 8.3% PER ADAAG 4.1.6.(H)
APPROPRIATE ACCESSIBLE SIGNAGE INDICATING LOCATION
OF ACCESSIBLE ENTRANCE WILL BE REQUIRED AT SOUTH DOOR.
3.) AT FRONT EAST DOOR PROVIDE APPROACH RAMP OF 1:12 MAX WITH WINGS OF 1:10 MAX.
12/19/2002 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) THRESHOLD INTO HANDICAPPED RESTROOMS MUST COMPLY WITH APAAG GUIDE LINES.
2.) MENS'S HC RESTROOM WILL NEED 18" CLEAR FROM WALLS OR OBSTRUCTIONS TO CENTER OF TOILET
3.) I WILL REVIEW SOUTH RAMP REGS AND LET YOU KNOW.