Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/07/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) BEARING WALLS FRAMED WITH STUDS AT 24" ON CENTER MUST HAVE DOUBLE TOP PLATE-SEE PAGE 3 2) WINDOWS REQUIRE AT LEAST DOUBLE 2 X 4 HEADERS BEARING ON KING STUDS AND TRIMMER 3) DOUBLE 2 X 8 BEAM MUST BEAR ON AT LEAST DOUBLE 2 X 4 POSTS AT EACH END 3) HANGERS REQUIRED ON ALL RAFTERS 4) HEADERS REQUIRED AT DOOR WAY |