Permit: T02CM04451

Parcel: 110113610


Addresses:

2480 N SWAN RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/09/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ CR-1 PNL SCH OK. DAIRY CASE CEILING OK. LIGHTS NORTHWEST END OK.
09/04/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1) PANEL SCHEDULE FOR "CR-1" NEED TO BE CORRECT AND PERMANENT. 2) CK DAIRY CASE NEXT TIME.
08/28/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/1) USE APPROVED FITTINGS FOR M/C CABLE ABOVE DAIRYCASE. 2) COMPLETE UNDERLINED ITEMS FROM PREVIOUS INSPECTION DATED 5/17/03.
05/27/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
05/01/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK PREVIOUS INSPECTION FROM 4/30/03.
04/30/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O PHOTO AREA.
04/29/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*NO FURTHER INSPECTIONS UNTIL BOND IS POSTED AND FULL APPROVED PLAN ARE ON SITE.
04/11/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O SUBJECT TO BOND.
1.) PROTECT DATA CABLES PREVIOUS INSP #4.
04/10/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) MAINTAIN WORKING CLEARENCE FOR W/H DISCONNECT.
2.) FINISH INSTALLATION OF DEVICES.
3.) ISOLATED GROUND TO HAVE YELLOW MARKER.
4.) PROTECT DATA CABLES.