Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T02CM04451
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2003 | ELECTRIC - ABOVE CEILING | Approved | ||
08/28/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* | |
05/27/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*/ 1) FINISH SUPPORTING WIRE FOR FIXTURES IN FRONT OF DAIRY CASE 2) EXPOSED CONDUCTORS AND LOOSE CONDUIT ABOVE CEILING 3) SEAL UNUSED OPENINGS IN LIGHTS IN DAIRY CASE 4) PLANS TO REFLECT WORK DONE TO NEW DAIRY CASE (POWER) 5) SUPPORT CONDUIT AND TIGHTEN LOOSE FITTINGS ABOVE DAIRY CASE-SEAL BEFORE ENTERING CASE 6) MISSING JUNCTION BOX COVER-EXPOSED CONDUCTORS ABOVE DAIRY CASE 7) SUPPORT M/C CABLE ABOVE DAIRY CASE, ABOVE OFFICES NEXT TO CUSTOMER SERVICE 8) FIXTURE TO BE SUPPORTED AS PER CODES. SUPPORT WIRES AND ATTACHED TO GRID 9) PANEL CR TO BE LABELED ON OUTSIDE OF COVER, ALSO CIRCUIT DIRECTORY NOT INSTALLED, AND MISSIHNG COVER SCREWS, FILL UNUSED OPENINGS, INSTALL STRANDED CONDUCTORS FULLY UNDER TERMINATIONS AND CLEAN EXCESS DIRET CUT OFF PANEL 10) NEED NEW TRANSFORMER OPENED UP FOR INSPECTION 11) REINSTALL FIXTURE ENTRANCE COVER 12) SUPPORT STRIP FIXTURES AS PER CODE AND WE HAVE EXPOSED CONDUCTORS. FILL UNUSED OPENINGS | |
05/21/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*/ 1) FINISH SUPPORTING NEW M/C CABLE AS PER CODE ALSO INDEPENDENT SUPPORT 300-11 2) POLL OF DATA CABLE LAYING ON FIXTURE 3) OK 2 X 4'S (3) AT ENTRY | |
05/20/2003 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) CANCELLED BY OFFICE | |
05/01/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* | |
04/28/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) IDENTIFY GROUNDED & GROUNDING CONDUCTORS IN BOXES 2.) BOND JUNCTION BOX ENCLOSURE OK CEILING AT PHOTO SHOP EXCEMPT AS NOTED. |
|
04/24/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* 1.) PHOTO AREA, FLEXABLE CONDUIT AN MC CABLE TO BE INDEPENDENTLY SUPPORTED TO STRUCTURE AND AT INTERVALS SPECIFIED IN 350-18 NEC. 2.) CONDUITS TO BE ISOLATED FROM PLUMBING. 3.) THIN WIRE NOT APPROVED FOR FIXTURE SIEZMIC. 4.) VERIFY GROUNDS IN FLEX CONDUIT. 5.) SUPPORT ALL J-BOXES GRID WIRES USED AS SUPPORT TO BE TIED BOTH ENDS. |
|
04/09/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999*FIXTURES TO BE ATTACHED GRID. 2.) CONDUIT TO BE SUPPORTED AS PER 300-11 AND BOXES. 3.) FILL UNUSED OPENINGS IN BOXES. 4.) STRAP CONDUITS AND M/C CABLE ON WEST WALL BY WINDOW. 5.) SUPPORT VDV CABLES UP OFF GRID. 6.) LIGHTING DOES NOT MATCH PLANS PLEASE REVISE PLANS OR INSTALL AS PER PLANS. |