Permit: T02CM04451

Parcel: 110113610


Addresses:

2480 N SWAN RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T02CM04451

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/09/2003 ELECTRIC - ABOVE CEILING Approved
08/28/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
05/27/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) FINISH SUPPORTING WIRE FOR FIXTURES IN FRONT OF DAIRY CASE 2) EXPOSED CONDUCTORS AND LOOSE CONDUIT ABOVE CEILING 3) SEAL UNUSED OPENINGS IN LIGHTS IN DAIRY CASE 4) PLANS TO REFLECT WORK DONE TO NEW DAIRY CASE (POWER) 5) SUPPORT CONDUIT AND TIGHTEN LOOSE FITTINGS ABOVE DAIRY CASE-SEAL BEFORE ENTERING CASE 6) MISSING JUNCTION BOX COVER-EXPOSED CONDUCTORS ABOVE DAIRY CASE 7) SUPPORT M/C CABLE ABOVE DAIRY CASE, ABOVE OFFICES NEXT TO CUSTOMER SERVICE 8) FIXTURE TO BE SUPPORTED AS PER CODES. SUPPORT WIRES AND ATTACHED TO GRID 9) PANEL CR TO BE LABELED ON OUTSIDE OF COVER, ALSO CIRCUIT DIRECTORY NOT INSTALLED, AND MISSIHNG COVER SCREWS, FILL UNUSED OPENINGS, INSTALL STRANDED CONDUCTORS FULLY UNDER TERMINATIONS AND CLEAN EXCESS DIRET CUT OFF PANEL 10) NEED NEW TRANSFORMER OPENED UP FOR INSPECTION 11) REINSTALL FIXTURE ENTRANCE COVER 12) SUPPORT STRIP FIXTURES AS PER CODE AND WE HAVE EXPOSED CONDUCTORS. FILL UNUSED OPENINGS
05/21/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*/ 1) FINISH SUPPORTING NEW M/C CABLE AS PER CODE ALSO INDEPENDENT SUPPORT 300-11 2) POLL OF DATA CABLE LAYING ON FIXTURE 3) OK 2 X 4'S (3) AT ENTRY
05/20/2003 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED BY OFFICE
05/01/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
04/28/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) IDENTIFY GROUNDED & GROUNDING CONDUCTORS IN BOXES
2.) BOND JUNCTION BOX ENCLOSURE
OK CEILING AT PHOTO SHOP EXCEMPT AS NOTED.
04/24/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
1.) PHOTO AREA, FLEXABLE CONDUIT AN MC CABLE TO BE INDEPENDENTLY SUPPORTED TO STRUCTURE AND AT INTERVALS SPECIFIED IN 350-18 NEC.
2.) CONDUITS TO BE ISOLATED FROM PLUMBING.
3.) THIN WIRE NOT APPROVED FOR FIXTURE SIEZMIC.
4.) VERIFY GROUNDS IN FLEX CONDUIT.
5.) SUPPORT ALL J-BOXES GRID WIRES USED AS SUPPORT TO BE TIED BOTH ENDS.
04/09/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*FIXTURES TO BE ATTACHED GRID.
2.) CONDUIT TO BE SUPPORTED AS PER 300-11 AND BOXES.
3.) FILL UNUSED OPENINGS IN BOXES.
4.) STRAP CONDUITS AND M/C CABLE ON WEST WALL BY WINDOW.
5.) SUPPORT VDV CABLES UP OFF GRID.
6.) LIGHTING DOES NOT MATCH PLANS PLEASE REVISE PLANS OR INSTALL AS PER PLANS.