Permit: T02CM04444

Parcel: 130050060

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
02/26/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*ALL CORRECTIONS HAVE BEEN MADE.
02/24/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) GAS PRESSURE TEST IS OK
2.) WASTE & VENT SYSTEM IS OK
3.) SOIL WATER TEST IS OK
4.) WATER SUPPLY TO WASHER BOX APPEARS TO BE LEAKING @ PEX TO COPPER CONNECTION.
02/21/2003 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*HAD MEETING WITH PLBG. CONTRACTOR ON GAS SYSTEM
02/14/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) APPROVED DRAWING SHOWS 80' OF DEVELOPED LENGTH BUT ACCUAL DEVELOPED LENGTH IS LONGER RE CALCULATE DEVELOPED LENGTH AND BTU TO CFH DEMAND AND GET A REVISED & APPROVED DRAWING SHOWING. THE INCREASE OF LINE THAT WILL BE REQUIRED.
2.) HAVE BTU & CFH. DEMAND CALC. OUT ON APPROVED DRAWING.
01/30/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) GAS LINES ARE NOT TO APPROVED DRAWINGS.
2.) SOIL WATER TEST IS OK
3.) OVERHEAD WATER DISTRIBUTION IS OK
4.) IF GAS METER HAS BEEN RELOCATED THEN A REVISED & APPROVED PLAN WILL BE NEEDED PRIOR TO NEXT INSPECTION.