Permit: T02CM04443

Parcel: 130050080

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/24/2003 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*SENT TO TEP ON 1/27/03 AT 9:15AM #1 AND #2.
01/22/2003 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*
1.) THE OUTLET BOX FOR THE GFI RECEPTACLE TO BE SUPPORTED NOT JUST BY OFF SET NIPPLE.
2.) THE GROUNDING BUSHING ON THE 2 1/2" RISER INSIDE THE SERVICE TO HAVE A #4 BC.
CONNECTING THE BUSHING TO ENCLOSURE 99NEC 250-94 UNPROTECTED CONDUCTORS AND CONDUIT GOING THUR CONCENTRIC KO'S.