Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/24/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*SENT TO TEP ON 1/27/03 AT 9:15AM #1 AND #2. | |
| 01/22/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* 1.) THE OUTLET BOX FOR THE GFI RECEPTACLE TO BE SUPPORTED NOT JUST BY OFF SET NIPPLE. 2.) THE GROUNDING BUSHING ON THE 2 1/2" RISER INSIDE THE SERVICE TO HAVE A #4 BC. CONNECTING THE BUSHING TO ENCLOSURE 99NEC 250-94 UNPROTECTED CONDUCTORS AND CONDUIT GOING THUR CONCENTRIC KO'S. |