Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T02CM04434
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/10/2003 | ELECTRIC - CABLE DROP | Denied | RISER CLAMP TO BE SECURLY MOUNTED TO STRUCTURE IT IS MOUNTED INTO A LOOSELY FASTENED SINGLE LAP OF SIDING. 2.) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE. |
|
| 03/13/2003 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000*sent to tep on 3/14/03 at 9:15am | |
| 03/05/2003 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* 1.) THE ELECTRICAL SERVICE REQUIRES A MINIMUM OF 36" CLEAR SPACE IN FRONT OFF THE TREE IS APROX 30" OR LESS. 110-26 A NEC. 2.) THE RISER COMING UP THE UTILITY SECTION WILL HAVE UNPROTECTED CONDUCTORS IN IT, THE PLASTIC BUSHING MUST BE REPLACED WITH A GROUNDING BUSHING AND A #6 COPPER ATTACHING BUSHING TO CON. 250-94. N.E.C. 3.) SUPPORT 3/4" CONDUITS UNDER SERVICE AND TRENCH HAS TO BE 24" DEEP ALL THE WAY TO TEP BOX. |