Inspection Status: Partial Approval
Inspection History: ELECTRIC - UNDERGROUND
| Date |
Description |
Inspector |
Results |
Comments |
| 10/17/2002 |
ELECTRIC - UNDERGROUND |
|
Partial Approval |
IVRS - Inspection 0000*OK U.G. CONDUIT UNDER PARKING AREA/DRIVE WAY AND 10' FROM PAVEMENT TO BLD. SOUTHWEST CORNER, PEDISTAL NOT INSTALLED YET. |
| 10/14/2002 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0999*THE 99 NEC REQUIRES THE CONDUIT TO BE A COMPLETE 24" BELOW GRADE THE PLAN ALSO STATES THIS IN SOME AREAS THERE IS ONLY 16" SAME ONLY 18" ALL CONDUIT TO BE 24" BELOW GRADE. 2.) WHAT IS 2ND UNFINISHED CONDUIT IN RAY MAJUTA FRENCH FOR ON WEST SIDE. |
| 10/11/2002 |
ELECTRIC - UNDERGROUND |
|
Denied |
IVRS - Inspection 0245*1. U.G. CONDUIT MUST BE 2' BELOW DRIVEWAYS. PARKING LOTS, PER 300-5 NEC. 2.) REPLACE PVC DAMAGED BY OVERHEATING. 110-12,90-4 NEC. |