Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/07/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 11/06/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 11/05/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) GIRDER TRUSS REQUIRES 3-2 X 4 POST AT BEARING 2) DETAIL (17/DT1) CALLS FOR 8D NAILING 6" ON CENTER 3) PORCH COLUMNS MUST BE PER DETAIL (3/DT1) 4) PORCH TRUSS INTERFACE MUST BE PER DETAIL (1/A2) 5) BLOCKING BETWEEN TRUSSES CALLS FOR 8D AT 6" ON CENTER NAILING 6) SOME STUD CLIPS MISSING AT BEARING 7) SW5 AT REAR REQUIRES 4" ON CENTER EDGE NAILING |
| 11/04/2002 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |