Permit: T02CM04400

Parcel: 126134810


Addresses:

4635 E 22ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
01/23/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
01/22/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*INSTALL ADDRESS LABEL FOR SERVICE EQUIP.
2.) NEED TO VERIFY UFER APPROVAL AT SWITCHGEAR.
3.) PVC CONDUIT STUB UPS INTO SWITCH GEAR TO LOW, WILL ALLOW RAIN WATER TO ENTER, RAISE UP TO AT LEAST 1"-2".
4.) COMPLETE SIGN OFF SHEET FOR TEMP POWER FOR TEST
5.) BOND GAS PIPING
6.) SUPPORT EMT, BOXES MC CABLE PER NEC. ARTS 348, 334,300.
01/07/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*BUILD 1
BUILD THE BAY CANOPY.
BUILD #3 AND 4 SOFFIT LIGHTING INTERMEDIATE
INTERIOR ABOVE CEILING APPROVED
12/04/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*HARD LID AREAS & J BOXES.