Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 01/22/2003 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*INSTALL ADDRESS LABEL FOR SERVICE EQUIP. 2.) NEED TO VERIFY UFER APPROVAL AT SWITCHGEAR. 3.) PVC CONDUIT STUB UPS INTO SWITCH GEAR TO LOW, WILL ALLOW RAIN WATER TO ENTER, RAISE UP TO AT LEAST 1"-2". 4.) COMPLETE SIGN OFF SHEET FOR TEMP POWER FOR TEST 5.) BOND GAS PIPING 6.) SUPPORT EMT, BOXES MC CABLE PER NEC. ARTS 348, 334,300. |
|
| 01/07/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*BUILD 1 BUILD THE BAY CANOPY. BUILD #3 AND 4 SOFFIT LIGHTING INTERMEDIATE INTERIOR ABOVE CEILING APPROVED |
|
| 12/04/2002 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*HARD LID AREAS & J BOXES. |