Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T02CM04393
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2002 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000OK FOR C OF O. | |
11/01/2002 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999*VARI FLOW CEILING DIFFUSER CANNOT REPLACE A DUCT SMOKE DETECTOR. 2.) FINISH DUCT CONNECTION TO COLLAR ON ROUND CEILING GRILLE NEAR ACCESS OPENING & FINISH SPIRAL DUCT CONNECTION NEAR FRONT OF STORE. OK FOR TEMP C OF O. | |
10/31/2002 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* DUCT SMOKE DETECTOR MUST BE AHEAD OF ALL OUTLETS ON SHOWROOM UNIT. SEAL IDNT CONNECTION AT END OF RETURN AIR IN SHOWROOM. INSTALL CONDENSATE DRAIN LINES TO AC UNITS HOOK UP ECONOMIZERS RECALL FOR INSPECTION. BLDG. INSPECTOR CAN CONFIRM CORRECTION IF HE CHOOSE TO. |