Permit: T02CM04383

Parcel: 138243070


Addresses:

2034 W BELLAGIO DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/08/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
01/07/2003 BUILDING - FINAL Denied IVRS - Inspection 0935*/ 1) WATER HEATER "B" VENT PLUGGED WITH TAPE 2) ATTIC ACCESS OBSTRUCTED BY A/C CONDENSATE 3) NO PRIOR INSPECTION REPORT ON SITE 4) NO LADDER ACCESS TO ATTIC TO INSPECT ELECTRIC
01/06/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) ITEM 3, 4, 5 AND 6 FROM PRIOR INSPECTION NOT REQUIRED
01/03/2003 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) A/C NOT CONNECTED TO POWER 2) A/C DISCONNECT WORK AREA OBSTRUCTED BY CONDENSER 3) ELECTRIC SERVICE PANEL MISSING COVER LATCH 4) WATER HEATER "B" VENT PLUGGED WITH TAPE
01/02/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*