Permit: T02CM04376

Parcel: 111081420


Addresses:

3525 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/03/2002 ELECTRIC - INTERMEDIATE Approved
11/27/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
10/14/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*THE 2 X 4 DROP IN LITE FIXTURES IN THE BREAK ROOM AND STORAGE ROOM ARE NOT SCREWED INTO THE GRID METAL. PLEASE COMPLETE THIS 2.) RUN A BONDING JUMPER AROUND THE DIELECTRIC UNION ON INCOMING WATER LINE TO ENSURE INTERIOR WATE PIPING IS GROUNDED. 3.) THE MAGIC MARKER LETTERING ON CIRCUIT BREAKERS IS SMUDGED AND NOT LEGIBLE. USE THE CIRCUIT DIRECTORY TO I.D. CIRCUITS AND PLEASE USE PEN, PENCIL OR SHARPIE. I.D. SHOULD BE LEGIBLE.