Permit: T02CM04364

Parcel: 11306061B


Addresses:

1701 E LIND RD

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/16/2003 FRAMING Approved IVRS - Inspection 0000*
07/10/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE TEST ON WATER LINES DWV'S 2) WATER LINES NOT COMPLETED IN BATHROOM 3) NAIL PROTECT ALL PLUMBING WITHIN 1 1/2 FROM EDGE OF STUD 4) WATER LINE AT MASTER BEDROOM, RUNNING HORIZONTAL AT TJI MUST BE VALVE PROTECTED ON MOVED UP TO HAVE A 1 1/2 CLEARANCE FROM BOTTOM OF TJI 5) PROVIDE APPROVED REPAIR FOR OVER NOTCHED BEARING STUD AT BATHROOM RIGHT SIDE OF WINDOW