Inspection Status: Partial Approval
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/07/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WILL RE-INSPECT INTERMEDIATES AT PERMANENT SITE 2) NO GAS IN HOUSE AS PER KIRBY (SUPER) |
| 02/06/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) DOUBLE TOP PLATE AT MASTER CLOSET OVER NOTCHED REQUIRES STRAPS IN 6 EACH 16D NAILS ON EACH SIDE 2) WATER LINES AND DWV'S NO TEST 3) PROTECT ALL PLUMBING WITHIN 1 1/2 FROM EDGES OF STUDS 4) EXHAUST FAN IN HALL BATH NOT CONNECTED TO EXHAUST LINE 5) GAS LINE NOT INSTALLED 6) SEE PREVIOUS INSPECTIONS |
| 01/30/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PLUMBING FOR RE-VENTING PURPOSE TEE'S MUST BE INSTALLED WITH SWEEP GOING UP (WOULD BE UPSIDE DOWN FOR DRAIN) 2) A. ELECTRIC-MAKE UP ALL GROUNDS IN ALL BOXES B. METAL CEILING BOXES MUST BE GROUNDED 3) PRESSURE TEST WATER AND DWV SYSTEMS 4) MECHANICAL REGISTERS MUST BE SUPPORTED ON 3 SIDES 5) EXTEND ELECTRIC HOME RUNS INTO MAIN PANEL 6) INSTALL GAS LINES AND PROVIDE PRESSURE TEST |
| 01/28/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) ALL OTHER TRADES, PLBG, ELECT, AND MECH SHALL BE COMPLETED PRIOR TO FRAME INSPECTION 2) STAPLE LATH AT 6" ON CENTER TOP AND BOTTOM EDGE |